Understanding Fan Curves.pdf

(135 KB) Pobierz
F AN E NGINEERING
®
FE-2000
Information and Recommendations for the Engineer
Understanding Fan Curves
Introduction
This document contains introductory material designed
to familiarize the user with the conventions and terminol-
ogy related to fan curves. Various axial and centrifugal
fan performance curves will be illustrated throughout this
article with no attempt made to rationalize any particular
selection. For a more in-depth look into the character-
istics of different fan types, refer to FE-2300 for axial
fans and FE-2400 for centrifugal fans.
Pressure Volume Curve
The most important characteristic of a fan or a system
is the relationship that links the primary variables asso-
ciated with its operation. The most commonly used fan
characteristic is the relationship between pressure rise
and volume flow rate for a constant impeller speed
(RPM). Similarly the relationship between pressure loss
and volume flow rate is the most commonly used sys-
tem characteristic.
Fan pressure rise characteristics are normally
expressed in either total pressure (TP) or static pressure
(SP), with static pressure being the units most com-
monly used in the United States. The fan volume flow
rate (airflow) is commonly expressed in cubic feet per
minute, or CFM. Therefore, the system pressure loss and
volume flow rate requirements are typically expressed as
a certain value of static pressure (SP) at some CFM.
The fan “pressure-volume” curve is generated by con-
necting the fan to a laboratory test chamber. By follow-
ing very specific test procedures as outlined in the Air
Movement and Control Association (AMCA) Standard
210, data points are collected and plotted graphically for
a constant RPM, from a “no flow” block off condition
to a “full flow” or wide condition. Figure 1 represents
such a curve that is typical for a vaneaxial fan, and is
commonly referred to as a “static pressure” curve.
Point A represents the point of zero airflow on the
static pressure curve. It is frequently referred to as “block
off,” “shut off,” “no flow,” and “static no delivery.”
Point B depicts the stall region of the static pressure
curve. Operation in this area is discouraged because of
erratic airflow that generates excessive noise and vibra-
tion. For a more in-depth look into this phenomenon
refer to ED-600, “Surge, Stall & Instabilities in Fans.”
Point C depicts what is referred to as the peak of
the static pressure curve, and point D is the point of
maximum airflow. Point D is also referred to as “free
delivery,” “free air,” “wide open performance,” and “wide
open volume.”
Curve segment CD is often referred to as the right
side of the fan curve. This is the stable portion of the
fan curve and is where the fan is selected to operate.
It then follows that curve segment AC is the left side
of the fan curve and is considered to be the unstable
portion of the curve.
Figure 1 is a vaneaxial curve with a pronounced dip
(stall region) that is also a typical curve shape for high
Figure 1. Static Pressure Curve, Vaneaxial
A
6
5
B
STALL
REGION
C
4
3
2
1
D
0 0
1
2
3
4
5
6
CFM
Figure 2. Static Pressure Curve, Backward Inclined
Centrifugal
7
C
6
A
5
4
3
2
1
D
0 0
1
2
3
4
5
6
7
8
9
CFM
angle propeller fans and forward curve centrifugal fans.
In contrast, compare this curve to Figure 2, which rep-
resents a typical curve for a backward inclined centrifu-
gal fan. This curve shape is also representative of
radial blade centrifugal fans.
Note the lack of a pronounced dip on this curve.
Nevertheless, the area left of peak is also a stall region
and selections in this area should be avoided.
The fan static pressure curve is the basis for all air-
flow and pressure calculations. For a given SP on the
static pressure curve there is a corresponding CFM at
a given RPM (see Figure 3).
©2001 Twin City Fan Companies, Ltd.
1474741687.081.png 1474741687.092.png 1474741687.103.png 1474741687.114.png 1474741687.001.png 1474741687.012.png 1474741687.023.png 1474741687.034.png 1474741687.035.png 1474741687.036.png 1474741687.037.png 1474741687.038.png 1474741687.039.png 1474741687.040.png 1474741687.041.png 1474741687.042.png 1474741687.043.png 1474741687.044.png 1474741687.045.png 1474741687.046.png 1474741687.047.png 1474741687.048.png 1474741687.049.png 1474741687.050.png 1474741687.051.png 1474741687.052.png 1474741687.053.png 1474741687.054.png 1474741687.055.png 1474741687.056.png 1474741687.057.png 1474741687.058.png 1474741687.059.png 1474741687.060.png 1474741687.061.png 1474741687.062.png 1474741687.063.png 1474741687.064.png 1474741687.065.png 1474741687.066.png 1474741687.067.png 1474741687.068.png
Figure 3. Static Pressure Curve, Vaneaxial
Figure 5. Static Pressure/Horsepower Curve
Backward Inclined Centrifugal
6
7
7
5
6
6
5
5
4
4
4
3
3
3
2
2
2
1
1
1
0 0
1
2
3
4
5
6
0 0
CFM
1
2
3
4
5
6
7
8
9
CFM
Simply locate some unit of pressure on the left hand
SP scale and project a horizontal line to the point of
intersection on the static pressure curve. From the point
of intersection project a vertical line to the bottom CFM
scale to establish the corresponding airflow at that par-
ticular speed. In this example a static pressure of three
units results in a CFM of 4.71 units.
Even though the performance curves for the vane-
axial fan and the centrifugal fan have completely differ-
ent shapes, the curves are read in the same way.
Locate some unit of pressure on the left hand SP scale
(4 units) and project a horizontal line to the point of
intersection with the SP curve. Projecting downward
from this point of intersection to the CFM scale we
establish an airflow of 6.55 units. Now project vertically
upward to intersect the BHP curve. Project a horizontal
line from this point to the BHP scale and read a BHP
of 6.86 units.
Brake Horsepower Curve
Having established a static pressure (SP) and an airflow
(CFM), an operating brake horsepower (BHP) can be
established (Figure 4).
Operating Point
The operating point (point of operation or design point)
is defined as the fan pressure rise (SP)/volumetric flow
rate (CFM) condition where the fan and system are in a
stable equilibrium. This corresponds to the condition at
which the fan SP/CFM characteristic intersects the sys-
tem pressure loss/flow rate characteristics.
Figure 6 illustrates this fan/system operating point using
the centrifugal fan performance curve from Figure 5.
Figure 4. Static Pressure/Horsepower Curve, Vaneaxial
6
12
5
10
4
8
Figure 6. Fan/System Operating Point,
Backward Inclined Centrifugal
3
6
2
4
7
7
1
6
6
2
5
5
0 0
4
1
2
3
5
6
CFM
SYSTEM
LINE
OPERATING
POINT
4
4
By adding the BHP curve to the static pressure curve
from Figure 3 we complete the fan performance curve.
To determine BHP simply extend vertically the CFM
point established in Figure 3 until it intersects the BHP
curve. Draw a horizontal line from this point of intersec-
tion to the right to the BHP scale to establish a BHP of
7.27 units, which corresponds to the previously estab-
lished performance of 4.71 CFM units at 3.0 SP units.
Similarly, we can add the BHP curve to the static
pressure curve of the backward inclined centrifugal fan
from Figure 2 to complete that fan performance curve
(Figure 5).
3
3
2
2
1
1
0 0
1
2
3
4
5
6
7
8
9
CFM
Page 2
Fan Engineering FE-2000
1474741687.069.png 1474741687.070.png 1474741687.071.png 1474741687.072.png 1474741687.073.png 1474741687.074.png 1474741687.075.png 1474741687.076.png 1474741687.077.png 1474741687.078.png 1474741687.079.png 1474741687.080.png 1474741687.082.png 1474741687.083.png 1474741687.084.png 1474741687.085.png 1474741687.086.png 1474741687.087.png 1474741687.088.png 1474741687.089.png 1474741687.090.png 1474741687.091.png 1474741687.093.png 1474741687.094.png 1474741687.095.png
The system line is simply a parabolic curve made up
of all possible SP and CFM combinations within a given
system and is determined from the fan law that SP var-
ies as RPM 2 . Another fan law states that CFM varies as
the RPM. Therefore, we can also say that SP varies as
CFM 2 . Note: Some systems have modulating dampers
which will not follow this parabolic curve.
Sometimes a fan system does not operate properly
according to the design conditions. The measured air-
flow in the fan system may be deficient or it may be
delivering too much CFM. In either case, it is necessary
to either speed the fan up or slow it down to attain
design conditions.
Knowing that the fan must operate somewhere along
the system curve, and knowing that it is possible to
predict the fan performance at other speeds by applying
the following fan laws:
1. CFM varies as RPM
2. SP varies as RPM 2
3. BHP varies as RPM 3
We can now graphically present an “operating line”
between various fan speeds using the fan/system oper-
ating point data from Figure 6. This results in new SP
curves and BHP curves as shown in Figure 7.
Figure 8. Variable System Characteristic Curve,
Backward Inclined Centrifugal
7
7
6
6
5
5
4
4
OPERATING
LINE
SYSTEM
LINES
3
3
2
2
1
1
0 0
1
2
3
4
5
6
7
8
9
CFM
Combining the fan control curve (Figure 7) with the
system controlled curve (Figure 8) results in a fan/system
controlled curve having an “operating region” as shown
in Figure 9.
Figure 7. Variable Fan Characteristic Curve,
Backward Inclined Centrifugal
Figure 9. Variable Fan/System Characteristic Curve
INCREASING
RPM
Backward Inclined Centrifugal
7
7
6
6
7
7
5
5
6
6
SYSTEM
LINE
OPERATING
LINE
4
4
5
5
INCREASING
SPEED (RPM)
3
3
4
4
OPERATING
REGION
2
2
SYSTEM
LINES
3
3
FAN
CHARACTERISTICS
1
1
2
2
0 0
1
2
3
4
5
6
7
8
9
1
1
CFM
0 0
These speed changes represent an example of fan
control that can be accomplished through drive changes
or a variable speed motor.
Another way to present an “operating line” is to add
a damper, making the system the variable characteristic.
By modulating the damper blades, new system lines are
created resulting in an operating line along the fan
curve. This can be seen graphically in Figure 8.
1
2
3
4
5
6
7
8
9
CFM
Conclusion
The foregoing methodology provides the knowledge nec-
essary to understand fan curves. When used in conjunc-
tion with FE-100, FE-600, FE-2300 and FE-2400, it
provides the user with the working knowledge necessary
to understand the fan performance characteristics and
capabilities of different fan equipment.
Page 3
Fan Engineering FE-2000
1474741687.096.png 1474741687.097.png 1474741687.098.png 1474741687.099.png 1474741687.100.png 1474741687.101.png 1474741687.102.png 1474741687.104.png 1474741687.105.png 1474741687.106.png 1474741687.107.png 1474741687.108.png 1474741687.109.png 1474741687.110.png 1474741687.111.png 1474741687.112.png 1474741687.113.png 1474741687.115.png 1474741687.116.png 1474741687.117.png 1474741687.118.png 1474741687.119.png 1474741687.120.png 1474741687.121.png 1474741687.122.png 1474741687.123.png 1474741687.124.png 1474741687.002.png 1474741687.003.png 1474741687.004.png 1474741687.005.png 1474741687.006.png 1474741687.007.png
®
AERovENt | www.AERovENt.com
5959 trenton Lane N | minneapolis, mN 55442 | Phone: 763-551-7500 | Fax: 763-551-7501
1474741687.008.png 1474741687.009.png 1474741687.010.png 1474741687.011.png 1474741687.013.png 1474741687.014.png 1474741687.015.png 1474741687.016.png 1474741687.017.png 1474741687.018.png 1474741687.019.png 1474741687.020.png 1474741687.021.png 1474741687.022.png 1474741687.024.png 1474741687.025.png 1474741687.026.png 1474741687.027.png 1474741687.028.png 1474741687.029.png 1474741687.030.png 1474741687.031.png 1474741687.032.png 1474741687.033.png
Zgłoś jeśli naruszono regulamin